Open-heart retrofit for one of europe’s largest dairies: From S5 to Plant iT V9.

It’s the long-awaited transformation to the next level. This software retrofit for one of our most loyal customers demonstrates how the modernization of a large dairy can be achieved not only efficiently but also with virtually no downtime. In the process, we sent the S5 controller—a true industrial dinosaur—into well-deserved retirement and, through a streamlined migration to a modern Plant iT V9 environment, ensured greater control, transparency, and safety in the process.

50

%
More redundancy

Initial situation

Legacy software that has evolved over time is reaching its limits

The retrofit involved a central unit area of the dairy through which key process steps are carried out and whose failure would have an immediate impact on the entire production process. The existing automation system consisted of a control system that had evolved over decades but was prone to errors, making maintenance, troubleshooting, and future scalability extremely difficult. This served as a strategic obstacle to the plant’s further development.
  • Faulty and unreliable Siemens S5 controller with Interbus connection
  • Many legacy issues and ad hoc solutions resulting from nearly three decades of operation
  • Confusing program structures and incomplete documentation
  • A growing shortage of personnel with S5 expertise

The challenge

In just 16 months, make the automation of the entire powertrain division ready for the coming decades without further shutting down the heart of production.

Clear objectives for the project

Modernization without significant production downtime

Replacement of the S5 and ProLeiT OSNT Software

Integration into the existing software and MES landscape

Restructured, clearly separated process areas

State-of-the-art safety technology that meets dairy industry standards

Improved maintainability and scalability

Solution

From 1.0 to Industry 4.0 in just 16 months

In a clearly defined and coordinated process, the outdated S5 control software from the 1990s was replaced by a future-proof Plant iT V9 control system. In the process, the software was thoroughly restructured, migrated to current hardware, and divided into separate process areas—resulting in significantly improved redundancy and transparency. Close monitoring of production ensured that fine-tuning and implementation could be carried out without disrupting day-to-day operations.
1

Analysis and current status assessment

Comprehensive on-site assessment in close coordination with senior management and division leadership
2

Concept

Inventory of existing hardware and software, assignment of the accumulated program components to specific process areas, and creation of a procedure description to serve as the basis for reprogramming
3

Rebuilding in Plant iT V9

Development of a new, unified software architecture; reprogramming of the step sequences in Plant iT V9; implementation of a modern Profinet infrastructure to replace the Interbus peripherals; and the simultaneous implementation of a new, user-friendly process visualization system
4

Testing and migration planning

Comprehensive functional acceptance testing (FAT) of the new solution, as well as the creation of a commissioning plan for the phased transition of individual step sequences. Temporary interfaces between S5 and S7 ensured that the old and new systems could communicate securely with each other during the transition phase.
5

Step-by-Step commissioning during production

All migrations took place within tightly scheduled windows—coordinated with production and cleaning cycles. This allowed the individual areas to be migrated to the new software and hardware platform with minimal downtime.

Advantages

The retrofit offers both operational and strategic benefits for operators and users.

Structured software

Clear assignment to process areas makes troubleshooting and adjustments easier.

Future-proof technology

Standardized components and modern Profinet infrastructure reduce inventory and simplify the procurement of replacement parts.

Improved maintainability

Safe operation of the systems, even for personnel without an S5 background.

Greater integration

Into the MES system and the existing IT infrastructure.

State-of-the-art safety technology and comprehensive documentation

Promote transparency and compliance.

Implementation with minimal downtime

Basically on the fly, with reliable project support.

automation excellence

Maximum transparency with maximum availability. Our modernization meets all the requirements that KRITIS companies place on their processes and infrastructure.

20% less interface load

through standardized structures

50% more redundancy

through clearly separated process areas

100% more user-friendliness

in visualization and user interface logic

1-second screen refresh rate

virtually in real time, reduced from 10 to 1 second

Open-heart surgery a success! Together with our client and partners, we have successfully achieved an important milestone on the path to a smart dairy.

Jens FiebigProkurist und Projektleiter
Porträt eines freundlich lächelnden Mannes im weißen Hemd.

Our partners

Strong Teamwork for a Successful Transformation

bawaco logo with a red line and the slogan know how in food processing

Conclusion

With the replacement of the old S5 and OSNT systems and the migration to Plant iT V9, the dairy’s core operations were brought up to the latest technological standards. The combination of structured software, modern Profinet infrastructure, and state-of-the-art safety technology reduces risks, simplifies maintenance, and increases efficiency throughout the entire process. At the same time, the new, unified software structure lays the foundation for further steps toward digitalization—from deeper MES integration to future big data applications.